Automatic Diesel Fire Water Pump

Fire pump series

Automatic Diesel Fire Water Pump

Silenced Diesel Water Pump System

Used for emergency water supply in high buildings, taper water, steel factories, wine plants, chemical factories, hotels. Automatic, full functions, good structure, easy to install and use.

    As per head, flow and media, the flow range: 10-870L/s, pressure range: 0.15-6MPa, diesel engine rotation speed range: 1500-2900rpm. 
    Used for emergency water supply in high buildings, taper water, steel factories, wine plants, chemical factories, hotels. Automatic, full functions, good structure, easy to install and use.
    as per conditions: 1-stage 1-priming centrifugal pump, high-pressure multi-stage pump, 2-priming pump.


     

    Run conditions:
    1. Altitude: ≤2500m
    2. Ambient temperature: -25~55ºC
    3. Ambient relative humidity: 9~95%
    4. Anti-earthquake degree: degree 7
    5. Flow range: 50-700(L/S)
    6. Head range: 32-600m
    7. Power: 18-1100KW
    8. Wet part materials: cast iron, graphite cast iron, stainless steel, cast copper.


    Function specifications:
    Diesel engine fire pump, electric pumps and stabilized pressure pump can form an automatic voltage fire water supply system and can realize linkage with fire control center. When diesel engine fire pump group received orders, if utility without powertime, then automatically control cabinet of diesel power immediately to the starter of pump group issued open signal, the starter, enggine idle starting, then gradually adjust diesel engine accelerator and make the diesel engine speed until the rated speed. The control system will automatic monitoring of diesel engine, such as the workings of diesel oil, oil temperature, rotational speed and pump outlet pressure, etc. Through the automatic monitoring to determine whether the normal starting diesel, if starting failure criterion control system will be issued to start signal, if 13 times are starting, the automatic control system failure will be issued starting failure alarming. When diesel engine fire pump group received pipe pressure recovery or mains supplyicoil resume normal signal, pump group will rapidly slow down and in idle position monitor after a period of automatic stop.



    Automatic-Diesel-Fire-Water-Pump.jpg
     

     

    Technical parameters:

     

      Q (L/s) (MPa) n (r/min) P (Kw) η (%)
    XBC3.0/5-50(65) 5 0.30 2900 4 63
    XBC3.2/5-50(65) 0.32
    XBC3.4/5-50(65) 0.34
    XBC4.6/5-50(65) 5 0.46 2900 7.5 58
    XBC4.8/5-50(65) 0.48
    XBC5.0/5-50(65) 0.50
    XBC7.6/5-50(65) 5 0.76 2900 15 50
    XBC7.8/5-50(65) 0.78
    XBC8.0/5-50(65) 0.80
    XBC11/5-50(65) 5 1.10 2900 30 40
    XBC12/5-50(65) 1.20
    XBC12.5/5-50(65) 1.25
    XBC3.0/10-65(80) 10 0.30 2900 7.5 71
    XBC3.2/10-65(80) 0.32
    XBC3.4/10-65(80) 0.34
    XBC4.6/10-65(80) 10 0.46 2900 15 67
    XBC4.8/10-65(80) 0.48
    XBC5.0/10-65(80) 0.50
    XBC7.6/10-65(80) 10 0.76 2900 22 59
    XBC7.8/10-65(80) 0.78
    XBC8.0/10-65(80) 0.80
    XBC11/10-65(80) 10 1.10 2900 37 54
    XBC12/10-65(80) 1.20
    XBC12.5/10-65(80) 1.25
    XBC3.0/25-80(100) 25 0.30 2900 15 76
    XBC3.2/25-80(100) 0.32
    XBC3.4/25-80(100) 0.34
    XBC4.6/25-80(100) 25 0.46 2900 22 74
    XBC4.8/25-80(100) 0.48
    XBC5.0/25-80(100) 0.50
    XBC7.6/25-80(100) 25 0.76 2900 37 69
    XBC7.8/25-80(100) 0.78
    XBC8.0/25-80(100) 0.80
    XBC11/25-80(100) 25 1.10 2900 75 69
    XBC12/25-80(100) 1.20
    XBC12.5/25-80(100) 1.25
    XBC13/25-80(100) 25 1.30 2900 90 57
    XBC14/25-80(100) 1.40
    XBC15/25-80(100) 1.50
    XBC3.0/45-125 45 0.30 2900 22 73
    XBC3.2/45-125 0.32
    XBC3.4/45-125 0.34
    XBC4.6/45-125) 45 0.46 2900 37 77
    XBC4.8/45-125 0.48
    XBC5.0/45-125 0.50
    XBC7.6/45-125 45 0.76 2900 55 80
    XBC7.8/45-125 0.78
    XBC8.0/45-125 0.80
    XBC11/45-125 45 1.10 2900 90 70
    XBC12/45-125 1.20
    XBC12.5/45-125 1.25
    XBC2.8/55-150 55 0.28 1450 30 78
    XBC3.0/55-150 0.30
    XBC3.2/55-150 0.32
    XBC4.6/55-150 55 0.46 1450 45 75
    XBC4.8/55-150 0.48
    XBC5.0/55-150 0.50